AGS stops generator ~15 minutes after starting

Issue:
Generator only turns on for 15 mins without fully charging my batteries.

Product Line:
Conext Automatic Generator Started

Environment:
Inverter system with generator backup

Cause:
AGS Stop triggers are not set to desired configuration. Either the StopV trigger or the StopAbsorb are selected.

Resolution:
If the StopV trigger is enabled, make sure the voltage selected is not close to the Start Voltage.

When a full battery charge cycle is desired with the generator make sure to select StopFloat trigger instead of StopAbsorb. StopFloat will stop the generator at the end of the Absorption Stage (end of charging cycle) while StopAbsorb will stop generator at the end of the Bulk Stage (first charging stage).

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings