Can you run a smaller test motor on a ATV630 and ATV930 drive?

Issue:
Running a smaller test motor on an ATV630 and ATV930 drive.

Product Line:
ATV630 and ATV930

Resolution:
You will need to set up the drive to run the smaller test motor.
Programming:
Main Menu
Complete settings:
Motor Parameters
Motor Control Type=  Set to V/F 5 Points

In Simply Start menu set up your motor amps and HP to size of the test motor.

Be aware that you can run a smaller motor as long as the motor parameters in the drive will adjust low enough for the motor's specs.