Why does my ATV6XX / ATV9XX drive require a power cycle after pressing Stop on the keypad?

Resolution:

When a drive is configured for start/stop control from the terminal strip (2‑wire or 3‑wire control), pressing the Stop button on the keypad is treated as an emergency stop. As a result, the drive will not run again until power is removed and reapplied.

This behavior occurs because the drive expects both run and stop commands to come from the same control source. If the run command is issued from the terminal strip but a stop command is received from the local keypad, the drive interprets this as a stop command from an unexpected source. For safety, it responds by performing an emergency stop.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.