What are the UL listings and markings for class, division, group, and zone for the NEMA 7 and 9 "explosion proof" devices?
Product Line:
NEMA 7 and 9 Enclosed Molded Case Switches and Circuit Breaker Enclosures
Resolution:
The following table shows the UL Listing and marking for the NEMA 7 and 9 devices.
Currently, they are UL listed and marked for class, division, and group, but not for zone.
| Catalog number | NEMA 7 | NEMA 9 | Product Type |
| H60XFA | X | X | Enclosed Molded Case Switch |
| H60XFA1212 | X | X | Enclosed Molded Case Switch |
| H100XFA | X | X | Enclosed Molded Case Switch |
| H100XFA1212 | X | X | Enclosed Molded Case Switch |
| H225XJG | X | X | Enclosed Molded Case Switch |
| H225XJGAA | X | X | Enclosed Molded Case Switch |
| FA060X | X | Circuit Breaker Enclosure | |
| FA100X | X | Circuit Breaker Enclosure | |
| J225X | X | Circuit Breaker Enclosure | |
| FA060Y | X | Circuit Breaker Enclosure | |
| FA060Y | X | Circuit Breaker Enclosure | |
| J225Y | X | Circuit Breaker Enclosure |
NEMA 7
Class I, Division 1 and 2, Groups C and D
Class II, Division 1 and 2, Groups E, F and G
Class III, Division 1 and 2
NEMA 9
Class II, Division 1 and 2, Groups E, F and G
Class III, Division 1 and 2
Released for: Schneider Electric USA
Explore more
Product:
Explore more
Product:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.