Why is the display screen on my Altivar Process Drive blank?

Article available in these languages:

Resolution:

If the display screen on your Altivar Process Drive is blank, follow these steps to troubleshoot the issue:

Check the display connection
If the display is remotely mounted, connect it directly to the front of the drive to confirm the display and cable are working properly.

Verify control power supplies
Measure the voltage at the +10 VDC and +24 VDC terminals relative to COM. Both voltages should be present for proper display operation.

Confirm correct communication cabling
If the drive is monitored or controlled via communications, ensure the Ethernet cable is connected to the correct Ethernet port and not mistakenly plugged into a Modbus or HMI port.

Check the DC bus voltage
If Ethernet wiring is correct and the +10 VDC and +24 VDC supplies are missing, measure the voltage between terminals PA and PC at the bottom of the drive:

    • Approximately 650 VDC on a 460 V system
    • Approximately 340 VDC on a 230 V system

Evaluate the control block
If the DC bus voltage is correct but +10 VDC and/or +24 VDC are not present at the control terminals, the control block has failed and should be replaced.

Verify incoming line voltage
If no DC bus voltage is present at PA–PC, measure the line voltage from L1, L2, and L3 to ground to confirm proper input power to the drive.

Determine if the drive has an internal fault
If line voltage at L1/L2/L3 is correct but the DC bus voltage is low or zero, the drive likely has an internal issue. Perform a static check on the inputs to confirm.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.