How can we help you today?

Is there possibility to assign temperature from PT100 to analog output on Altivar Process variable speed drive ATV630 or to read it by communication ?

Unfortunately this is not possible. Analog output cannot be assigned to motor temperature provided by PT100.
However TH2V value (AI2 thermal value when AI2 assigned to PT100) can be read by communication. Address 13250, range -15 .. + 200 degrees Celsius.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.