How do I program an ATV61 or ATV71 drive to use a 0–10 VDC speed reference on AI1?

Resolution:

To configure an ATV61 or ATV71 drive to follow an external 0–10 VDC speed reference on Analog Input AI1, follow these steps from the keypad:

Access the Main Menu
Press the ESC or Menu key to enter the main menu.

Open the Drive Menu

  • Navigate to and select Drive Menu (DRC).

Configure the command reference

  • Enter the Command Menu (CtL)
  • Set Reference 1 channel (Fr1) to AI1

Enable reference switching

  • Go to the Application Function Menu (Fun)
  • Enter Reference Switching (rEF-)
  • Set Reference 1B switching (rEF1b) to Channel 1 Active

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.