How do I program the ATV61 analog output for an 0-10Vdc feedback?
Issue:
Program the ATV61 analog output for an 0-10Vdc feedback .
Product Line:
ATV61 / ATV71
Environment:
All serial numbers
Cause:
Need feedback signal
Resolution:
Main menu > Drive > Input / output menu > Set AO1 type to "IOU". Set UOL1 to 0 and UOH1 to 10.
Program the ATV61 analog output for an 0-10Vdc feedback .
Product Line:
ATV61 / ATV71
Environment:
All serial numbers
Cause:
Need feedback signal
Resolution:
Main menu > Drive > Input / output menu > Set AO1 type to "IOU". Set UOL1 to 0 and UOH1 to 10.
Released for: Schneider Electric USA