What is the terminal cover for a 2 pole, H frame breaker?
Issue:
Does the 2p H frame breaker have an optional terminal cover?

Product Line:
Circuit Breakers

Resolution:
The answer depends on the following:
1. Is it a 2 pole HD, HG, HJ, or HL breaker?
  • If HD or HG, there are no optional terminal covers for the 2 pole versions.
  • If HJ or HL, go to the next question.
2. Is it an I-line breaker, which has prefix HJA or HLA?
  • If HJA or HLA, the terminal shield is part number HDTC. Quantity of 1 for the load end.
3. Is this a unit mount breaker such as HJL or HLL, and what is the amp rating?
  • If HJL or HLL, the 15 - 60 A terminal shield is part number S37446. Quantity of 2, one for each end.
  • If HJL or HLL, the 70 - 150 A terminal shield is part number S37447. Quantity of 2, one for each end.