How do I configure the RY relay on an ATV212 drive to activate when a speed threshold is reached?

Resolution:

You can configure the RY relay on the ATV212 drive to activate when the motor speed (output frequency) reaches a defined threshold.

Follow these steps:

  1. Set the relay function

    • Go to: I/O Menu → RY Relay Function (F130)
    • Ensure F130 = 4 (Freq. 1 reached / Speed reached)
    • This is the factory default setting in most cases.
  2. Define the speed (frequency) threshold

    • Set parameter: F100 (Freq. 1 reached)
    • Enter the desired frequency value (in Hz) at which the relay should activate
  3. (Optional) Configure delay

    • Use F146 (RY delay) if you want to delay relay activation after the threshold is reached

Result:
The RY relay energizes when the drive output frequency is equal to or greater than the value set in F100, and de-energizes when it drops below that value.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.