How can we help you today?
What demand parameters are available in PM1130H meter ?
Issue:
Need to identify the demand values, demand calculation methods, and available demand measurements supported by the PM1130H meter.
Product Line:
PM1130H meter
Environment:
Viewing demand information locally on the meter and/or through communications
Monitoring applications where demand history, peak tracking, and demand calculation method selection are required
Cause:
Demand reporting varies by device. Users need to know which demand values, peak timestamping, calculation methods, and reset options are available on the PM1130H.
Resolution:
The PM1130H provides the following demand-related parameters and functions:
- Demand values available:
- Last demand
- Present demand
- Maximum (Peak) demand
- Timestamp via counters indicating when the maximum (peak) demand occurred
- Supported demand calculation methods:
- Sliding block
- Fixed block
- Rolling block
- Peak demand reset options:
- Manual reset (password protected)
- Reset through communication
- Demand measurements include (Total):
- W (Demand)
- VAR (Demand)
- VA (Demand)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.