Does Unity Pro have a cascade PID function block?
Issue:
Cascade PID function blocks in Ecostruxure Control Expert(Unity Pro)
Product Line:
Unity Pro, Ecostruxure Control Expert
Resolution:
Yes. There are two cascade control loop function blocks. The function blocks are PIP and PPI. The PIP consists of a PI(Proportional Integral)-master controller and a P(Proportional)-sub-controller. The PPI consists of a P(Proportional)-master controller and a PI(Proportional Integral)-sub-controller.
The transfer function is as follows:
PIP
Master controller (PI- controller) ---> G(s) = gain2 x { 1 + 1/(ti x s) }
Sub controller (P- controller) ---> G(s) = gain1
PPI
Master controller (P-controller) ---> G(s) = gain1
Sub controller (PI- controller) ---> G(s) = gain2 x { 1 + 1/(ti x s) }
Cascade PID function blocks in Ecostruxure Control Expert(Unity Pro)
Product Line:
Unity Pro, Ecostruxure Control Expert
Resolution:
Yes. There are two cascade control loop function blocks. The function blocks are PIP and PPI. The PIP consists of a PI(Proportional Integral)-master controller and a P(Proportional)-sub-controller. The PPI consists of a P(Proportional)-master controller and a PI(Proportional Integral)-sub-controller.
The transfer function is as follows:
PIP
Master controller (PI- controller) ---> G(s) = gain2 x { 1 + 1/(ti x s) }
Sub controller (P- controller) ---> G(s) = gain1
PPI
Master controller (P-controller) ---> G(s) = gain1
Sub controller (PI- controller) ---> G(s) = gain2 x { 1 + 1/(ti x s) }
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.