What basic programming changes are required when replacing an ATV66 with an ATV630 in a Trane unit?

Resolution:

When replacing an ATV66 drive with an ATV630 in a Trane unit, you must update the wiring assignments and key parameters to match the new drive’s configuration. These are the Key Programming and Wiring Changes:

1. Digital Inputs (DI) Reassignment

  • Run Forward command:
    • ATV66: LI2 → Run Forward
    • ATV630: Move LI2 wire to DI1 (Run Forward)
  • Run Permissive (Enable):
    • ATV66: LI1 → Run Permissive
    • ATV630: Move LI1 wire to DI2 (nSt / Stop)

2. Stop Configuration

  • Go to: Complete Settings → Generic Functions → Stop Configuration
  • Assign Freewheel Stop to DI2

3. Reverse Command

  • Go to: Complete Settings → Command and Reference
  • Set Reverse Assignment = NO

4. Analog Input (AI)

  • ATV66 had a temperature sensor (resistive type) assigned to AI2. This input is not used on ATV630
  • Configure AI1 as Frequency Reference:
    • Path: 5. Complete Settings → 5.5 Command and Reference → Ref Frequency 1 Config = AI1

5. Hand/Auto Switching

  • ATV66: LI3 used for Hand/Auto selection
  • ATV630:
    • Set DI3 to “Ref 1B Switching”
    • Path: 5. Complete Settings → 5.5 Command and Reference → Ref 1B Switching = DI3

6. Fault Reset

  • ATV66: LI4 used for fault reset
  • ATV630:
    • Assign DI4 as Fault Reset
    • Path: 5. Complete Settings → 5.12 Error/Warning Handling → Fault Reset → Fault Reset Assign = DI4
These changes ensure that the ATV630 replicates the original ATV66 control logic while aligning with updated parameter structure and input mapping. Always verify wiring and test operation after programming.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings