Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the dwell Setting / Time for Hi pot testing a V5D7133Y000A, 15kV/40kA (750MVA) vacuum circuit breaker?
Issue:
For testing a V5D7133Y000A breaker, what would be the time for Hi-pot test, and at what voltage?

Product Line:
VR Vacuum breaker

Environment:
Maintenance

Cause:
Testing

Resolution:
This a V5D7 VR breaker , 15kV/40kA ), (750MVA) ,  and should be Hi-Pot tested @ 36kV V(RMS) for a 1 minute Dwell / per phase.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings