What is the breaker suffix used for 2 pole , single phase, Powerpact B breakers ?
Issue:
Breaker suffix for phasing with Powerpact B breakers for 2 pole selection
Product Line:
Powerpact B Breaker
Environment:
Application
Cause:
Load balance
Resolution:
The breaker suffix's are listed below :
1 = AB phasing
2 = AC phasing
3 = BA phasing
4 = BC phasing
5 = CA phasing
6 = CB phasing
Breaker suffix for phasing with Powerpact B breakers for 2 pole selection
Product Line:
Powerpact B Breaker
Environment:
Application
Cause:
Load balance
Resolution:
The breaker suffix's are listed below :
1 = AB phasing
2 = AC phasing
3 = BA phasing
4 = BC phasing
5 = CA phasing
6 = CB phasing
Released for: Schneider Electric USA