How can we help you today?

Is the 24 Vdc power supply for Micrologic trip units supposed to be grounded or ungrounded?

Issue:
Does it matter whether the 24Vdc power supply for Micrologic Trip Units is grounded or ungrounded?

Product Line:
Micrologic Trip Units

Resolution:
The attached document, 48041-084-01, is included in the carton with the Micrologic trip units. On the second page, it states that the 24 Vdc power must not be grounded.

Schneider Electric USA

Attachment(s)
48041-084-01.pdf [82.08 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings