How can we help you today?

Error Initializing Cross Reference Cache in Application Modules Diagnostic View

Issue
Unable to edit sources or measurements on existing gadget or create new gadget. The application modules diagnostic view will include the following message:
Error initializing cross reference cache. ---> Framework.Common.Exceptions.ModuleException: Data Source Device [*****] is defined multiple times. where [*****] is the name of a device in the system.

Product Line

Power Monitoring Expert 7.2

Power Monitoring Expert 8.x

Power Monitoring Expert 9.x

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024


Environment
SQL Server Management Studio

Cause
Multiple entries in the [ApplicationModules].[DataSourceBus].[DataSourceDevice] and/or [ApplicationModules].[DataSourceBus].[LogicalDevice]  tables

Resolution
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*
A) Determine the LogicalDeviceId in the DataSourceDevice table
1) Use Applicationmodule
Select Description, count(*) from [DataSourceBus].[DataSourceDevice] group by [description]
having count(*) > 1


2) Use the description field in the query below;
Use Applicationmodules
Select Description, LogicalDeviceID, from [DataSourceBus].[DataSourceDevice] where [description] like '*******'


B) Remove the duplicate entries
1) Make backup of AppicaltionModuless database
2) Shut down the AppMods services
3) Run ApplicationModules-DeleteAllDeviceMetadata.sql attached (the device metadata will get rebuilt)
4) Run the following query where aaa,bbb,ccc are LogicalDeviceIds found in section A
-- delete duplicate devices
delete from DataSourceBus.datasourcedevice where DatasourcedeviceID in (aaa,bbb,ccc)
delete from DataSourceBus.logicaldevice where logicaldeviceID in (aaa,bbb,ccc)

5) Start the AppMods services
6) Check the Diagnostics.LogEvent table to verify that Data Source Bus initialized correctly

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.