Why would a LC1F115 chatter with a new LX1FF110 coil?
Issue:
Identify the cause why the LC1F115-F225 would chatter with a new LX1FF coil
Product Line:
Tesys F Contactors and Starters
Environment:
IEC Contactors and Starters
Resolution:
They have changed the magnet in the LC1F115 contactors and the LX1FF coils will no longer work. The existing LX1 type 50Hz or 60Hz coils cannot be used in contactors with Zinc coating magnets. LX9, LX4 and LXE coil types shall be used along with these new type magnets. Suitable marking are made on the product for the easy understanding of users. All new contactors manufactured with /without coil will be with Zinc coated magnets only.
See the attached Product information. It also lists the new coil part numbers.
Identify the cause why the LC1F115-F225 would chatter with a new LX1FF coil
Product Line:
Tesys F Contactors and Starters
Environment:
IEC Contactors and Starters
Resolution:
They have changed the magnet in the LC1F115 contactors and the LX1FF coils will no longer work. The existing LX1 type 50Hz or 60Hz coils cannot be used in contactors with Zinc coating magnets. LX9, LX4 and LXE coil types shall be used along with these new type magnets. Suitable marking are made on the product for the easy understanding of users. All new contactors manufactured with /without coil will be with Zinc coated magnets only.
See the attached Product information. It also lists the new coil part numbers.
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.