{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Is there a way to test the SDE overcurrent trip switch on PowerPacT circuit breakers?
Issue:
How is the SDE tested in PowerPacT breakers?

Product Line:
Circuit Breakers

Resolution:
The SDE overcurrent trip switch contacts are activated ONLY when the Micrologic trip unit causes the breaker to trip from an overload, short circuit, or ground fault. Therefore, the function of the SDE can be tested by tripping the breaker with primary or secondary injection testing. The SDE cannot be tested by pressing the red trip button, nor can it be tested by tripping the breaker with a shunt trip or undervoltage trip accessory.

Schneider Electric USA

Explore more
Product:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: