How do you configure the ATV320 drive for a bipolar +10/-10vdc speed control?

Article available in these languages:

Resolution:

To configure AI2 for a ±10 VDC input, use the following programming path:

CONF → FULL → I/O Menu → AI2 Configuration

Set the parameters as follows:

  • AI2t [AI2 Type]: Set to [Voltage +/-] (n10U) for a bidirectional ±10 VDC input.
  • UIL2 [AI2 Min Value]: Set to 0 V
  • UIH2 [AI2 Max Value]: Set to 10.0 V

Although the AI2 scaling parameters are set from 0 to 10 V, selecting n10U allows AI2 to accept a -10 V to +10 VDC signal.

With this configuration:

  • 0 to -10 VDC = Reverse (REV)
  • 0 to +10 VDC = Forward (FWD)

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.