How can we help you today?

When using a switch to trigger the Dry Run function on an ATV630 series drive, is it necessary to configure the Low flow / high flow parameters?

Article available in these languages:

  • Spanish

Issue:
Customer is using the Dry Run function of the ATV630 series to stop the motor in case of loss of prime on the pump.  They are using a float switch to trigger this function when the water level drops too low.  They need to know if it is still necessary to configure the low flow/low speed and high flow/high speed paramters that are used to sense dry run when a switch is not used.

Product line:
ATV630 series drives.

Environment:
All models, All serial numbers.

Cause:
Available literature is vague in this area.

Resolution:
No, it is not necessary to configure the Dry Run sensing parmaters when the dry run function is being triggered by a switch.  The switch will directly trigger the function, the sensing parameters will not be considered in this mode.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings