When Monitoring LCr (Motor Current) via Communication on ATV600 and ATV900 Drives, What Feedback Value Should Be Expected?

Article available in these languages:

Resolution:

When monitoring LCr (Motor Current) through communication on ATV600 (ATV6xx) and ATV900 (ATV9xx) drives, the reported value uses a scaling coefficient that depends on the drive rating.

  • Drive ratings up to D15: Coefficient = 0.01 A
  • Drive ratings from D18 to C16: Coefficient = 0.1 A
  • Drive ratings above C16: Coefficient = 1 A

LCr Unit: Amperes (A)

To determine the actual motor current, apply the appropriate coefficient based on the drive rating.