What is the recommended wire size and torque rating for the VW3A3600 module adapter grounding screw?
Over torquing the VW3A3600 module ground screw may strip the threads.
The recommended wire size is AWG 14 size wire and the recommended torque is 4.4 lb-in or 0.5 Nm
See the attached instruction bulletin.
*******