Why ports are not available for selection inside E-configurator modbus master scanner or How to setup modbus master scanner with modbus slave device with scadapack RTU ?

Yes its observed that when ports 1 or port 2 is to be selected inside modbus scanner of e-configurator through "ADD DEVICE"  button  Port selection field is empty and Port 1 and Port 2 is not available for selection.
To make it appear assign Port 1 function field in 'Ports' to Modbus master ( Modbus RTU) in Ports configuration . Refer screen shot below.

modbus slave device with scadapack RTU

Later go to Modbus Scanner ---> Add Device ---> Select correct port like port 1 or port 2.

modbus slave device with scadapack RTU


Final step is to configure scanner line inside scanner table with all the information related to modbus protocol to make communication successful.

modbus slave device with scadapack RTU