How to disable Field Bus Monitoring on an ATV320 drive [video]
Question:
How to disable Field Bus Monitoring on an ATV320 drive
Product String Reference:
Objective:
The objective of this video is to provide guidance of how to disable field bus monitoring on an ATV320 drive.
Product Line:
IDSDS – Speed Drives Systems.
Environment:
N/A
Resolution:
How to disable Field Bus Monitoring on an ATV320 drive
Product String Reference:
- Top Level > Product Category > Industry > Industry Control & Drives > Variable Speed Drives > Altivar 320.
- Top Level > PR_Product_OPS_Structure > Variable Speed Drives and Soft Starters > Low Voltage AC Machines Drives > Altivar Machine ATV320
Objective:
The objective of this video is to provide guidance of how to disable field bus monitoring on an ATV320 drive.
Product Line:
IDSDS – Speed Drives Systems.
Environment:
N/A
Resolution:
- Go to the COnF [Configuration Menu] and select “FULL”
- Scroll to “FLt” and press enter
- Scroll to “CLL” [Communications Module Parameter]
- Select CLL again
- Find “NO” to disable field bus monitoring
Released for: Schneider Electric USA