Why Can’t I Find the t90 (Initial Starting Torque) Parameter When Programming an ATS48?
Resolution:
The t90 (Initial Starting Torque) parameter is only available when Torque Control (CLP) is enabled.
If you cannot find the t90 parameter, check the DRC menu and verify that Torque Control (CLP) is set to Yes. When Torque Control is disabled, the t90 parameter is hidden and cannot be adjusted.
After enabling CLP, you can configure the t90 value between 20% and 100%, depending on the starting torque required for your application.