How can we help you today?
Why Can’t I Find the t90 (Initial Starting Torque) Parameter When Programming an ATS48?
Resolution:
The t90 (Initial Starting Torque) parameter is only available when Torque Control (CLP) is enabled.
If you cannot find the t90 parameter, check the DRC menu and verify that Torque Control (CLP) is set to Yes. When Torque Control is disabled, the t90 parameter is hidden and cannot be adjusted.
After enabling CLP, you can configure the t90 value between 20% and 100%, depending on the starting torque required for your application.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.