Can you use a box extension to add thru feed lugs to a NQ or NF panel?
Issue:
Does Schneider electric recommend using extensions, when adding sub or thru feed lug kits instead of replacing the enclosure with the correct size?

Product Line:
NQ and NF Panelboards

Environment:
Products sold in North America

Resolution:
No, this is not recommended.

Box extensions do not contain box studs so there is nothing to attach the mounting rails that come with the sub/feed thru lug kits.

In the case of the 400A and larger interiors, the longer box also means a longer vented trim.  This would move the vents on the trim down an additional 6 inches which allows the thru feed lugs to clear the trim vents.  Adding a box extension does not move the trim vents away from the lugs and that results in the lugs being too close to the vents and arcing can occur.