How can we help you today?

How to read Frequency of pulses on LI5 used as freq. input on Altivar 320 frequency inverter?

Yes, it is possible. But it is necessary at first to assign this frequency input to one of the variables. For example parameter FR2=RP. (No need to use FR2 as frequency reference at all).
Then from the register (logical address 13306, can open 16#2067/9) it is possible to read the frequency of LI5 input.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings