Can the Altivar 320 (ATV320) Run a Motor Above 60 Hz?
Resolution:
Yes. The Altivar 320 (ATV320) can operate a motor above 60 Hz if the application and motor are designed to support higher speeds.
To configure the drive:
- Navigate to CONF > FULL > SIM-.
- Set tFr (Maximum Frequency) to a value greater than 60 Hz.
- In the SIM- menu, set HSP (High Speed) to the desired operating frequency.
- Ensure that HSP does not exceed the tFr value.
Note: Before increasing the operating frequency above 60 Hz, verify that the motor and driven equipment are rated for the higher speed to avoid equipment damage or unsafe operation.