How do you control the speed of an Altivar 630 or Altivar 930 drive using the local HMI?

Resolution:

To control the motor speed of an Altivar 630 drive from the local HMI, you must change the speed reference source from the factory default (analog input) to the HMI. Follow the steps below from the drive keypad.


Configure Speed Control from the Local HMI

  1. Enter the Main Menu on the drive.
  2. Navigate to:
    Main Menu → Complete Settings → Command and Reference
  3. Set the following parameters:
    • HMI CMD → Set to Bumpless
      (Default is Disabled; this prevents sudden speed changes when switching control sources.)
    • Ref Freq 1 Config → Change from AI1 (factory default) to Ref Freq – Rmt Term

Important Additional Setting

  • If the Start/Stop command comes from the terminals, but speed control is performed from the HMI, you must change the Control Mode to Separate.
  • This allows different sources to be used for command (Run/Stop) and reference (Speed).



If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings