What Causes a bOF Braking Resistor Overload Fault on ATV900 Series Drives?

Resolution:
The drive generates this fault when the braking resistor thermal model detects an overload condition. One possible cause is incorrect configuration of the braking resistor parameters, particularly:

  • brP – Braking resistor power
  • brV – Braking resistor resistance
  • brtC – Braking resistor thermal time constant

The calculated thermal state of the braking resistor can be monitored using tHb [Braking Resistor Monitoring].

To troubleshoot, do the following:

  • Verify that the braking resistor is correctly sized for the application.
  • Confirm that the braking resistor parameters brP, brV, and brtC match the installed resistor specifications.Monitor tHb [Braking Resistor Monitoring] to check the calculated thermal state of the braking resistor.
  • Using SoMove, check the thermal states TH1R, TH2R, and TH3R in the Service section for additional diagnostic information.
  • If the fault persists with the correct settings, review the application's braking duty and confirm that the braking resistor is adequately sized for the required braking energy.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.