How can we help you today?
What would cause the ATV630 or ATV930 Process drives to trip out on a CFA error?
Issue:
What is the CFA fault code on the ATV630 or ATV930 Process drives?
Product Line:
ATV630 or ATV930
Environment:
All
Cause:
The monitoring function has detected an error on the digital input assigned to [CabinetCircuit A Assign].
CFA is active when the detected error duration is longer than [CabinetCircuit A Delay] FdA.
Resolution:
What is the CFA fault code on the ATV630 or ATV930 Process drives?
Product Line:
ATV630 or ATV930
Environment:
All
Cause:
The monitoring function has detected an error on the digital input assigned to [CabinetCircuit A Assign].
CFA is active when the detected error duration is longer than [CabinetCircuit A Delay] FdA.
Resolution:
| The fault can only appear if a cabinet input has been configured as Cabinet Circuit A error. The stop type when the fault appears is configurable. The acquisition time of LI is 2ms. Probable cause: The monitoring function has detected an error on the digital input assigned to [CabinetCircuit A Assign]. CFA is active when the detected error duration is longer than [CabinetCircuit A Delay] FdA. Remedies: • Check the connected device (door switch, thermal switch,…) and its wiring. • Check the parameters CFAA (high/low assignment of the cabinet IO) |
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.