Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the Short Circuit Rating For Class 8940 Pump Panels
Issue:
Information on the Class 8940—UL listed Short Circuit Ratings

Product Line:
Contactors and Starters

Environment:
Well-Guard Control™ Pump Panels

Resolution:
See table below.
NEMA SizeNEMA Fuse Class or VoltageEnclosureAvailable Amperes
RMS Symmetrical
Size 0–3Class H or KStandard5,000
Size 0–3Class RStandard100,000
Size 0–2Class H or KStandard5,000
Size 0–2Class RStandard100,000
Size 4-5Class H or KStandard10,000
Size 4-5Class RStandard100,000
Size 6Class H or KStandard18,000
Size 6Class RStandard100,000
Thermal-Magnetic Circuit Breaker Type
Size 0-50-480 VStandard100,000
Size 6-70-480 VStandard65,000
NOTE: Standard enclosures include non-oversize NEMA 1, 4 & 4X Stainless, and 12.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings