Can SoMove Monitor Multiple Altivar Process Drives Over a Modbus Network?

Resolution:
Yes. SoMove can be used to monitor multiple drives over a Modbus RTU network using a multipoint connection.

The drives can use their built-in Modbus RTU communication, so an additional gateway is not required for this configuration.

To set up the network:

  1. Assign a unique Modbus address to each drive.
  2. Connect the drives in a daisy-chain Modbus network.
  3. Compatible connection cables include:
    • VW3A8306TF03: 0.3 m (approximately 1 ft)
    • VW3A8306TF10: 1.0 m (approximately 3 ft)
  4. In SoMove, configure the scan as Multipoint.
  5. Configure the appropriate register range to be monitored.

Each drive on the network must have a unique Modbus address so that SoMove can identify and communicate with the individual devices.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.