There is an Auxiliary Alarm Output sensor. If that sensor is enabled and installed on an IO point (DO), the assigned DO will turn on any time there is an active alarm.
It does not turn on for alerts. The system cannot be configured so that a DO will turn ON only if a specific alarm is raised.
For instance you cannot configure it to turn on if the HH alarm is raised, but not turn on if the LL alarm is raised.
It does not turn on for alerts. The system cannot be configured so that a DO will turn ON only if a specific alarm is raised.
For instance you cannot configure it to turn on if the HH alarm is raised, but not turn on if the LL alarm is raised.