Where do I connect my auto mode run command, on an enclosed ATS22 soft starter system?
Issue:
Connecting Auto-Mode run command on an enclosed ATS22.
Resolution:
For Auto-mode run command on an ATS22 system, the run command will connect between terminals 5 and 6. This will be a "2-wire" type connection where the motor will run as long as this connection is closed and will stop when this connection opens.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.