Can ANY of the Canadian, 3 phase, QO, NEMA 3R, main breaker and main lug load centers be top or bottom fed?
Issue:
Product Design Features
Product Line:
QO 3-phase Load Centers
Resolution:
TOP FEEDING:
ALL of the Canadian, QO, 3 phase, NEMA 3R load centers come with the main breaker or main lugs located at the top of the load center interior and can be top fed as standard.
BOTTOM FEEDING:
NOTE: BOTTOM FEEDING OF THESE LOAD CENTERS WILL BE COMPLETELY DEPENDENT ON LOCAL CODE AUTHORITY ACCEPTANCE.
1) NO NEMA 3R, QO, 3 phase load center can be rotated, neither the interior nor the complete load center.
2) All of the Canadian, NEMA 3R, main lugs load centers can be bottom fed by entering the bottom endwall with the incoming conductors and running the conductors up past the interior, through the gutter area, and making a loop around into the main lugs.
3) NONE of the Canadian, NEMA 3R, main breaker load centers can be bottom fed due to the CSA required service entrance barrier.
Product Design Features
Product Line:
QO 3-phase Load Centers
Resolution:
TOP FEEDING:
ALL of the Canadian, QO, 3 phase, NEMA 3R load centers come with the main breaker or main lugs located at the top of the load center interior and can be top fed as standard.
BOTTOM FEEDING:
NOTE: BOTTOM FEEDING OF THESE LOAD CENTERS WILL BE COMPLETELY DEPENDENT ON LOCAL CODE AUTHORITY ACCEPTANCE.
1) NO NEMA 3R, QO, 3 phase load center can be rotated, neither the interior nor the complete load center.
2) All of the Canadian, NEMA 3R, main lugs load centers can be bottom fed by entering the bottom endwall with the incoming conductors and running the conductors up past the interior, through the gutter area, and making a loop around into the main lugs.
3) NONE of the Canadian, NEMA 3R, main breaker load centers can be bottom fed due to the CSA required service entrance barrier.
Released for: Schneider Electric USA
Explore more
Category:
Explore more
Category:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.