Can an ATV630 or other Altivar drive be used with motors having different numbers of poles, such as 2-pole, 4-pole, or 8-pole motors?

Yes. The drive does not require the number of motor pole pairs to be entered manually.

Program the drive using the motor nameplate information, making sure the Motor Rated Speed matches the RPM listed on the motor nameplate.

Typical motor speeds at 60 Hz are approximately:

  • 2-pole motor: 3600 RPM range
  • 4-pole motor: 1800 RPM range
  • 8-pole motor: 900 RPM range

For the ATV630 and other Altivar Process drives, enter the appropriate Motor Rated Current and Motor Rated Speed from the motor nameplate.

Equivalent parameters on other Altivar drives include:

  • ATV212: F415 and F417
  • ATV12 / ATV312 / ATV320 / ATV340: nCr (Motor Rated Current) and nSP (Motor Rated Speed)
  • ATV61 / ATV71 / Altivar Process: Motor Rated Current and Motor Rated Speed

The drive uses the programmed motor nameplate speed, so the motor's number of pole pairs does not need to be configured separately.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.