How do I initiate a backup on my LTMCUF keypad
Issue:
Tesys T unit with LTMCUF keypad shows F09 fault code when powered. Customer is not using the FDR function.
Product line:
Tesys T, LTMR, LTMCUF
Environment:
Tesys T systems equipped with LTMCUF remote keypad.
Cause:
On initial power a backup function must be performed to backup a copy of the program to the LTMCUF keypad.
Resolution:
To initiate a backup function, press and hold the 2 round buttons with green circles around them for 3-4 seconds. This will initiate a backup function and save a copy of the current program on the Tesys T into the keypad. After this has completed, cycle power on the LTMR and it should boot without the F09 fault code.
Tesys T unit with LTMCUF keypad shows F09 fault code when powered. Customer is not using the FDR function.
Product line:
Tesys T, LTMR, LTMCUF
Environment:
Tesys T systems equipped with LTMCUF remote keypad.
Cause:
On initial power a backup function must be performed to backup a copy of the program to the LTMCUF keypad.
Resolution:
To initiate a backup function, press and hold the 2 round buttons with green circles around them for 3-4 seconds. This will initiate a backup function and save a copy of the current program on the Tesys T into the keypad. After this has completed, cycle power on the LTMR and it should boot without the F09 fault code.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.