iEM3000 Series Demand Capabilities

Issue
To read Peak Demand values from the meter

Product Line
iEM3455
iEM3465
iEM3555
iEM3565

Cause
The newer iEM34xx and iEM35xx meters provide demand values

Resolution

Demand readings are available in the iEM34xx and iEM35xx models from the below firmware versions. iEM34xx and iEM35xx models with older firmware versions cannot be upgraded.

  1. iEM34x5 - V1.2.003 and higher
  2. iEM35x5 - V1.1.001 and higher
  3. iEM3465 and iEM3565 - BACnet V2.4 and higher
CharacteristicsDescription
Peak Demand Values (iEM3455, iEM3465, iEM3555, iEM3565)
CurrentPer phase, neutral, and average
Active, reactive, apparent powerTotal


In a nonvolatile memory, the power meter maintains a maximum operating demand value called peak demand. The peak is the highest value (absolute value) for each of these readings since the last reset.

For information on how to set up, reset or read demand values from meter registers, please refer to attached iEM3400/iEM3500 User Manual.

Schneider Electric USA

Attachment(s)
iEM3400-iEM3500 User Manual August 2023.pdf [2.36 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings