What would cause the ATV630 (or ATV930) M/S configured drives (Multidrive) not to start?
Resolution:
In a MultiDrive Master/Slave configuration, all slave drives must receive and maintain a valid run command before a run command is sent to the master drive.
If the master drive receives a run command before all slave drives have an active run command, the MultiDrive system will not start.
To resolve this issue:
- Verify that every slave drive has an active run command.
- Confirm the run commands are present on all slave drives before issuing the run command to the master drive.
- Reissue the run command to the master drive after all slave drives are ready.
Following the correct run command sequence ensures proper startup of the MultiDrive system.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.