What copper cable is used to connect at BMXNRP020x to a BMxCRA312x0 module?
Issue
What kind of copper cable is used to connect a BMXNRP020x fiber module to a BMxCRA312x0 Drop module?
Product line
M580, X80
Resolution
The BMXNRP020x to a BMxCRA312x0 connection is a standard RJ45 copper Ethernet connection. The maximum distance is less than 100m using shielded twisted 4-pair CAT5e or greater (10/100 Mbps) cable. (We do not recommend using twisted 2-pair CAT5e or CAT6 cables.)
Typically a customer will use anything that they already have available to them, at this link https://www.se.com/us/en/download/document/DIA6ED2140903EN/ you will find a catalog which includes a list of available ConneXium cables on page 24 (31). Any of the straight through will work.