How can we help you today?

How to roll back NetBotz firmware.

Issue:
How to roll back NetBotz firmware.

Product Line:
Netbotz

Environment:
NetBotz 3xx, 4xx, and 5xx firmware

Cause:
If for some reason you feel the need to revert back to a previous firmware (BotzWare) revision on a NetBotz appliance, you can not simply use the upgrade feature.


Resolution:
Follow the detailed instructions for the TFTP procedure highlighted in FA176133.

Replace step 1 with the version of BotzWare to which you are looking to downgrade. Older revisions may be available at: www.apc.com/tools/download

Please note that when downgrading, it is suggested that you not keep any of the old configuration and do not use the "rootupgkeep" option in step 17.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings