How can we help you today?

Why Is the Current Limitation Function on My ATV71 Drive Not Limiting Motor Current?

Resolution:
The Current Limitation (CLI) function becomes inactive if it is configured below the motor's no-load current. In this condition, the drive cannot effectively control motor operation and will not apply current limiting as expected. Incorrect motor parameter settings can also prevent the Current Limitation function from operating properly.

Verify the following settings:

1.- Current Limitation (CLI)

  • Ensure the CLI value is set higher than the motor's no-load current.
  • If CLI is set too low, the function will be inactive.

2.- Motor Rated Current

  • Confirm that the motor rated current parameter matches the value on the motor nameplate.

3.- Motor Thermal Current

  • Verify that the motor thermal current setting is correctly configured according to the motor nameplate data.

Accurate motor parameter configuration is essential for proper operation of the Current Limitation function. If the Current Limitation function is not operating as expected, review all motor nameplate settings and verify that the configured CLI value is appropriate for the application and motor characteristics.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.