How can we help you today?
How can the ATV212 be programmed for forced local?
Resolution:
The ATV212 supports Forced Local Mode, which can be activated using either of the following methods:
-
Permanent Forced Local Mode
- Set parameter F108 (Always Active Logic) to 48.
- This configuration keeps Forced Local Mode continuously active.
-
Forced Local Mode via RES Terminal
- Set parameter F113 (RES Terminal Function) to 48.
- Forced Local Mode will be activated whenever the RES terminal is energized or active.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.