How can the ATV212 be programmed for forced local?

Resolution:

The ATV212 supports Forced Local Mode, which can be activated using either of the following methods:

  1. Permanent Forced Local Mode

    • Set parameter F108 (Always Active Logic) to 48.
    • This configuration keeps Forced Local Mode continuously active.
  2. Forced Local Mode via RES Terminal

    • Set parameter F113 (RES Terminal Function) to 48.
    • Forced Local Mode will be activated whenever the RES terminal is energized or active.