How can we help you today?

What is the dissipated heat rating for ATV930 drives?

Issue:
Dissipated heat rating for ATV930 drives.

Product Line:
Altivar 930

Environment:
All

Cause:
Heat loss

Resolution:
Dissipated Heat Ratings

The first value is the power dissipated at a nominal current in the forced-cooled area of the drive.  The second value is the power dissipated at nominal current in the naturally cooled area, the value used in case of installation using the flush-mounting kit, separate hot and control part in the cabinet.  If the drive is installed in a standard cabinet, the sum of both values is to be taken into account.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.