When using Momentum with Control Expert, what does "Cause: Changeover from RUN to STOP by the terminal or dedicated input" indicate?

Issue
When online in the PLC configuration Task screen it indicates that last stop was "Changeover from RUN to STOP by the terminal or dedicated input".

Product line
Unity Pro, Control Expert, Momentum

Resolution
With the Momentum, this means that someone with a 'Terminal' such as Unity/ECE or OS Loader stopped the CPU.  The Momentum does not support a stop/start input bit.