In a BMXSPS4022 redundant power supply situation, what is the current draw on the “standby” power supply?
Issue
Do the M580 Redundant power supplies share the load?
Product line
Modicon M580, Modicon X80
BMXCPS3522, BMXCPS4022
Resolution
The Primary supply supports 100% (or close to 100%) of the load and the Standby 0%.
As far as sizing goes, the nominal draw of both power supplies must be accounted for. In a 24VDC setting, it will be 1.9 A + 1.9 A or 3.8 A
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Do the M580 Redundant power supplies share the load?
Product line
Modicon M580, Modicon X80
BMXCPS3522, BMXCPS4022
Resolution
The Primary supply supports 100% (or close to 100%) of the load and the Standby 0%.
As far as sizing goes, the nominal draw of both power supplies must be accounted for. In a 24VDC setting, it will be 1.9 A + 1.9 A or 3.8 A
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.