How can we help you today?

How do you program a relay on the ATV630 to close at speed reached

Article available in these languages:

Issue
The customer wants relay R1 to close when the motor reaches the commanded reference frequency.

Resolution
To configure relay R1 to activate when the reference frequency is reached:

  1. Navigate to Complete Settings → Input/Output → Relay → R1 Configuration → R1 Assignment.
  2. Set R1 Assignment to [Ref Freq Reached] (SrA) or Frequency Reference Reached.
  3. Once configured, relay contacts R1A and R1C will close when the motor frequency reaches or exceeds the reference frequency.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.