Example of VBScript that reads CSV files

DISCLAIMER

The example below is intended to demonstrate one or more features or methods and is presented as a configuration example only. Schneider Electric assumes no liability for the use or application of this example or any portion thereof.

Sometimes it is necessary to read a text file (.CSV in this case) in ClearSCADA. If the read is triggered by an operation action (clicking a button), a script can be used.
The example below shows one way to read a CSV file using VBScript. It reads only one line, but can be easily modified to read multiple lines:

sub Read1()
' Create object that will be used to read a file
Set fso = CreateObject("Scripting.FileSystemObject")
' Open the file for reading text; first parameter is the full file name with path
' The machine running the script must have access to the file

Set file = fso.OpenTextFile ("z:\zCSVtest.csv", 1)

' Read first (and only) line
line = file.Readline

' split the line in array entries; the values are separated by comma
arrValues = Split(line, ",")

' Assuming we are reading 3 values, double floats, store each element of the array in the proper point
Server.SetOPCValue ".A1", CDbl(arrValues(0))
Server.SetOPCValue ".A2", CDbl(arrValues(1))
Server.SetOPCValue ".A3", CDbl(arrValues(2))

' Close file
file.Close

msgBox "Done"

end sub


Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.